2. Wiring


2.1 Setting R Slider Tab

Use the built-in jumper (R Slider Tab) to appropriately configure the thermostat for one- or two- transformer systems.

  • If there is only one R wire, and it is connected to the R, Rc, or Rh terminal, set the slider to the Up position (1 wire).

  • If there is one wire connected to the R terminal and one wire connected to the Rc terminal, set the slider to the Down position (2 wires).

Note:The Slider Tab for U terminals should be left in place for T6 Pro models.


2.2 Wiring Terminal Designations

S

Input for wired indoor or outdoor sensors (TH6320U and TH6220U only)

S

Y

Compressor contactor (stage 1)

Y2

Compressor contactor (stage 2)

G

Fan

C

24VAC common. For 2 transformer systems, use common wire from cooling transformer.

U

Unused

U

L/A-A

Heat pump fault input. The Common wire (C) is required for LA/A.

O/B

Changeover valve

AUX-W2

Auxiliary heat or Heat (stage 2)

E

Emergency Heat

W

Heat (stage 1)

Note: Not to be used in heat pump applications

K

Unused

R

24VAC power from heating transformer

Rc

24VAC power from cooling transformer*

Note: Terminal can be jumped using R Slider Tab. See 2.1 Setting R Slider Tab above.


2.3 Wiring Conventional Systems: Forced Air and Hydronics

1H/1C System (1 Transformer)

R

Power [1]

Rc

(R+Rc joined by R Slider Tab) [2]

Y

Compressor contactor

C

24VAC common (Optional with batteries)

W

Heat

G

Fan

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R Slider Tab on UWP to the R setting. For more information, see “2.1 Setting R Slider Tab” above.

Heat-Only System

R

Power [1]

Rc

(R+Rc joined by R Slider Tab) [2]

C

24VAC common (Optional with batteries)

W

Heat

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R Slider Tab on UWP to the R setting. For more information, see “2.1 Setting R Slider Tab” above.

Heat-Only (Series 20)

R

Series 20 valve terminal “R” [1]

Rc

(R+Rc joined by R Slider Tab) [2]

Y

Power-closed terminal at valve

C

24VAC common (Optional with batteries)

W

Power-closed terminal at valve

In ISU set Heat System Type (ISU#200) to Radiant Heat (Option 3). Set number of Cool Stages (ISU#220) to 0.

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R Slider Tab on UWP to the R setting. For more information, see “2.1 Setting R Slider Tab” above.

Heat-Only (Power Open Zone Valve)

R

Power [1]

Rc

(R+Rc joined by R Slider Tab) [2]

C

24VAC common (Optional with batteries)

W

Heat

In ISU set Heat System Type (ISU#200) to Radiant Heat (Option 3). Set number of Cool Stages (ISU#220) to 0.

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R Slider Tab on UWP to the R setting. For more information, see “2.1 Setting R Slider Tab” above.

1H/1C System (2 Transformer R-Slider Down)

R

Power (heat transformer)[1]

Rc

Power (cool transformer)[1]

Y

Compressor contactor

C

24VAC common (Optional with batteries) [2]

W

Heat

G

Fan

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Common connection must come from cooling transformer.

Heat-Only System with Fan

R

Power [1]

Rc

(R+Rc joined by R Slider Tab) [2]

C

24VAC common (Optional with batteries)

W

Heat

G

Fan

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R Slider Tab on UWP to the R setting. For more information, see “2.1 Setting R Slider Tab” above.

Cool-Only System

R

Power [1]

Rc

(R+Rc joined by R Slider Tab) [2]

Y

Compresor contactor

W

Heat

G

Fan

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R Slider Tab on UWP to the R setting. For more information, see “2.1 Setting R Slider Tab” above.

2H/2C System (1 Transformer) (TH6320U/TH6220U only)

R

Power [1]

Rc

(R+Rc joined by R Slider Tab) [2]

Y

Compressor contactor (stage 1)

C

24VAC common (Optional with batteries)

W

Heat

G

Fan

W2

Heat (stage 2)

Y2

Compressor contactor (stage 2)

In ISU, set Heat System Type (ISU#200) to Conventional Forced Air Heat (Option 1), Cool Stages (ISU#220) to 2 and Heat Stages (ISU#221) to 2.

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R Slider Tab on UWP to the R setting. For more information, see “2.1 Setting R Slider Tab” above.


2.4 Wiring Heat Pump Systems

1H/1C Heat Pump System

R

Power [1]

Rc

(R+Rc joined by R Slider Tab) [2]

Y

Compresor contactor

C

24VAC common (Optional with batteries)

O/B

Changeover valve [3]

G

Fan

W

Do not use this terminal for heat pump applications!

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R Slider Tab on UWP to the R setting. For more information, see “2.1 Setting R Slider Tab” above.

[3] In ISU, set Reverse Valve O/B (ISU#218) to O: O/B in Cool (Option 0) or B: O/B in Heat (Option 1).

2H/1C Heat Pump System

R

Power [1]

Rc

(R+Rc joined by R Slider Tab) [2]

Y

Compresor contactor

C

24VAC common (Optional with batteries)

O/B

Changeover valve [3]

Aux

Auxiliary Heat

E

Emergency Heat

L

Heat Pump fault input

W

Do not use this terminal for heat pump applications!

In ISU, set Heat System Type (ISU#200) to Heat Pump (Option 2), Cool Stages (ISU#220) to 1 and Backup Heat Stages (ISU#221) to 1.

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R Slider Tab on UWP to the R setting. For more information, see “2.1 Setting R Slider Tab” above.

[3] In ISU, set Reverse Valve O/B (ISU#218) to O: O/B in Cool (Option 0) or B: O/B in Heat (Option 1).

2H/2C Heat Pump System (TH6320U only)

R

Power [1]

Rc

(R+Rc joined by R Slider Tab) [2]

Y

Compresor contactor (stage 1)

C

24VAC common (Optional with batteries)

O/B

Changeover valve [3]

G

Fan

Y2

Compresor contactor (stage 2)

L

Heat Pump fault input

W

Do not use this terminal for heat pump applications!

In ISU, set Heat System Type (ISU#200) to Heat Pump (Option 2), Cool Stages (ISU#220) to 1 and Backup Heat Stages (ISU#221) to 0.

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R Slider Tab on UWP to the R setting. For more information, see “2.1 Setting R Slider Tab” above.

[3] In ISU, set Reverse Valve O/B (ISU#218) to O: O/B in Cool (Option 0) or B: O/B in Heat (Option 1).

3H/2C Heat Pump System (TH6320U only)

R

Power [1]

Rc

(R+Rc joined by R Slider Tab) [2]

Y

Compresor contactor (stage 1)

C

24VAC common (Optional with batteries)

O/B

Changeover valve [3]

G

Fan

Aux

Auxiliary Heat

E

Emergency Heat

Y2

Compresor contactor (stage 2)

L

Heat Pump fault input

W

Do not use this terminal for heat pump applications!

In ISU, set Heat System Type (ISU#200) to Heat Pump (Option 2), Cool Stages (ISU#220) to 2 and Backup Heat Stages (ISU#221) to 1.

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R Slider Tab on UWP to the R setting. For more information, see “2.1 Setting R Slider Tab” above.

[3] In ISU, set Reverse Valve O/B (ISU#218) to O: O/B in Cool (Option 0) or B: O/B in Heat (Option 1).

Dual Fuel System (TH6320U / TH6220U only)

R

Power [1]

Rc

(R+Rc joined by R Slider Tab) [2]

Y

Compresor contactor (stage 1)

C

24VAC common (Optional with batteries)

O/B

Changeover valve [3]

G

Fan

Aux

Auxiliary Heat

E

Emergency Heat

Y2

Compresor contactor (stage 2 - If needed) [4]

L

Heat Pump fault input

S

Outdoor Sensor

S

Outdoor Sensor

W

Do not use this terminal for heat pump applications!

[1] Power supply. Provide disconnect means and overload protection as required.

[2] Move R Slider Tab on UWP to the R setting. For more information, see “2.1 Setting R Slider Tab” above.

[3] In ISU, set Reverse Valve O/B (ISU#218) to O: O/B in Cool (Option 0) or B: O/B in Heat (Option 1).

[4] Dual fuel with Y2 only for TH6320U.